Fluke 1650B Инструкция по эксплуатации онлайн [33/62] 4485

Fluke 1650B Инструкция по эксплуатации онлайн [33/62] 4485
Electrical Installation Tester
Making Measurements
25
4. Press 3 to select the RCD type. Valid types are:
E – Standard AC RCD, normal setting.
F – Pulse current sensitive RCD (Type A).
(Models 1652B and 1653B only)
E G – Delayed response AC RCD.
F G – Delayed response pulse current sensitive RCD.
(Models 1652B and 1653B only)
5. Press 4 to select the test current phase, 0° or 180°. RCDs should be
tested with both phase settings, as their response time can vary
significantly depending on the phase.
6. Press and release T. Wait for the test to complete.
The primary (upper) display shows the trip time.
The secondary (lower) display shows the fault voltage (N to PE)
related to the rated residual current.
If the trip time is according to the appropriate standard of the RCD and
the fault voltage is below the chosen limit (25V, 50V), the RCD W
indicator displays. For more information, see Maximum Trip Time
Table on page 50.
To measure RCD tripping time for a custom RCD setting – VAR mode:
1. Turn the rotary switch to the ΔT position.
2. Press 1 to select the VAR current rating. The current custom setting
shows on the primary display. Use the U arrow keys to adjust the value.
3. Press 2 to select a test current multiplier. Normally you will use x 1/2 or
x 1 for this test.
4. Repeat steps 4 through 6 listed in the preceding RCD tripping time
procedure.
5. To view the nominal setting used for the test, depress the U arrow key.
Note
The maximum setting for type A RCDs is 700 mA.
To measure RCD tripping time using Auto mode:
1. Plug the tester into the outlet.
2. Turn the rotary switch to the ΔT position.
3. Press 1 to select the RCD current rating (10, 30, or 100 mA).
4. Press 2 to select Auto mode.
5. Press 3 to select the RCD type.

Содержание

Скачать