Daikin EWWQ440AJYNN/A [32/130] User menu

Daikin EWWQ650AJYNN/A [32/130] User menu
The Digital Controller ESIE07-05
2–26 Part 2 – Functional Description
3
1
2
4
5
1.5.2 User Menu
In this menu you can set the parameters by entering the password and acceding the following masks:
Item description Default U.m.
Cooling Temperature SetPoint Limits 4.0-10.0 °C
Heating Temperature SetPoint Limits (only in heat pump or pursuit
mode)
40.0-50.0 °C
Setpoint reset
Return/4-20mA/OAT
NONE
Cooling setpoint 4-20mA
Override (if enabled) Limits for evaporator leaving water
4.0-10.0 °C
Cooling setpoint 4-20mA
Override Limits (if enabled) for condenser outlet water (only in heat
pump or pursuit mode)
40.0-50.0 °C
Return Temperature evaporator leaving water Setpoint Override Set (if
enabled)
Evaporator DT for no override setpoint / Max Setpoint diff.
3.0
3.0
°C
Double setpoint enabling N
TemperatureChLW
setpoint limits
Low
˚C
High
˚C
xx.x
xx.x
Lvg Water Temp.
setpoint reset
NONE
ChLWT
Override
Minimum
Maximum
Setpoint
Limits
˚C
˚C
xxx.x
xxx.x
4-20mA
enabled
ChLWT
Start
Max
Return
Reset
Dt
˚C
˚C
xx.x
xx.x
reset
Return
enabled
Enable
setpoint
double
N/Y
ESIE07-05.book Page 26 Friday, December 21, 2007 3:21 PM