Daikin EWWQ440AJYNN/A [64/130] Anti freeze alarm

Daikin EWWQ550AJYNN/A [64/130] Anti freeze alarm
Functional Control ESIE07-05
2–58 Part 2 – Functional Description
3
1
2
4
5
Function
description
In case the unit has 2 evaporators:
2 C
4 C
3 C
Anti-freeze Alarm
Setpoint
Freeze Prevention
Setpoint
Outlet Temp.
Time
possible for the
compressor to upload
possible to reset
Anti-freeze Alarm
Freeze up prevention
(load down)
Anti-freeze Alarm
(shutdown)
Anti-Freeze Alarm
Setpoint
Diff.
02.0 ˚C
01.0 ˚C
Evap 1 Anti-Freeze Alarm
Setpoint
Diff.
2.0 ˚C
1.0 ˚C
Evap 2 Anti-Freeze Alarm
Setpoint
Diff.
2.0 ˚C
1.0 ˚C
ESIE07-05.book Page 58 Friday, December 21, 2007 3:21 PM