Daikin FXSQ50P7VEB [120/370] Defrost operation

Daikin FXHQ32MVET [120/370] Defrost operation
Special Control SiBE311209
111 Function
8.3 Defrost Operation
Execute the defrost operation to recover the heating capacity by melting frost attached on the outdoor unit heat
exchanger during heating operation.
[Start conditions]
Referring to the following conditions, start defrost operation.
• When there is a decrease in the coefficient of heat transfer (1) of outdoor unit heat exchanger
• When there is a drop in the temperature of outdoor unit heat exchanger outlet (Tb)
• When the low pressure stays low for a certain amount of time (2 hours minimum)
1 The thermal continuity of outdoor unit heat exchanger is calculated by Tc, Te, and compressor loads.
<Outdoor unit>
Actuator
Electric
Symbol
In preparation
In defrosting
operation
After defrosting operation
Step 1 Step 2 Step 1 Step 2
Compressor 1 M1C 52 Hz
OFF
RTSQ10,
12PA: 232Hz
RTSQ14,
16PA: 210Hz
OFF
124 Hz
Increase the
operating
frequency in
increments of
2 steps per
20 sec. until
"Pc - Pe > 4MPa.
Compressor 2 M2C Maintaining
the current
step
ON OFF
Compressor 3 M3C ON OFF
Outdoor unit fan 1 M1F
Same step as
that in normal
heating
OFF OFF
Fan: Step 8 Fan: Step 8
Outdoor unit fan 2 M2F
Same step as
that in normal
heating
OFF OFF
Electronic
expansion valve
(Main)
Y1E
Same step as
that in normal
heating
480 pls 480 pls 480 pls 55 pls
Electronic
expansion valve
(Subcooling)
Y3E
Same step as
that in normal
heating
0 pls 0 pls 0 pls 0 pls
Electronic
expansion valve
(Refrigerant
charge)
Y2E 80 pls 80 pls 80 pls 80 pls 80 pls
Solenoid valve
(Refrigerant
regulator gas vent
pipe)
Y1S
Same step as
that in normal
heating
Same step as
that in normal
heating
Same step as
that in normal
heating
Same step as
that in normal
heating
Same step as that in normal
heating
Four way valve
(Heat changer
switch)
Y3S ON OFF OFF OFF ON
Solenoid valve
(Refrigerant
regulator liquid
pipe)
Y4S
Same step as
that in normal
heating
Same step as
that in normal
heating
Same step as
that in normal
heating
Same step as
that in normal
heating
Same step as that in normal
heating
Solenoid valve
(Hot gas)
Y5S
Same step as
that in normal
heating
ON OFF ON OFF
Solenoid valve
(Main bypass)
Y6S OFF ON ON ON OFF
Solenoid valve
(Refrigerant
regulator discharge
pipe)
Y7S
Same step as
that in normal
heating
Same step as
that in normal
heating
Same step as
that in normal
heating
Same step as
that in normal
heating
Same step as that in normal
heating
Solenoid valve
(Refrigerant
regulator discharge
pipe)
Y8S
Same step as
that in normal
heating
Same step as
that in normal
heating
Same step as
that in normal
heating
Same step as
that in normal
heating
Same step as that in normal
heating
Solenoid valve
(Heat exchanger
hot gas)
Y9S OFF ON ON ON Ta < 0 ON Ta > = 0 OFF
Four way valve
(High/low pressure
gas pipe switch)
Y2S OFF ON ON ON OFF
Ending Conditions 170 sec.
After
a lapse
of 1 min.
Pc - Pe
< 0.5MPa
After
a lapse
of 12 min.
Tb > 11°C
After
a lapse
of 1 min.
Pc - Pe
< 0.5MPa
After a lapse of
160sec.
Pc - Pe > 0.4MPa
&
OR
OR
OR
OR