Daikin FXSQ50P7VEB [93/370] When system is in stop mode

Daikin FXSQ63P7VEB [93/370] When system is in stop mode
SiBE311209 Stopping Operation
Function 84
2. Stopping Operation
2.1 When System is in Stop Mode
Both master units and slave units all stop according to the following contents.
2.2 Stop due to Error
In order to protect compressors, if abnormal conditions occur, the system will make "stop with thermostat OFF" and the
error will be determined according to the number of retry times.
(Refer to P.202~203 "List of Error Code" in Part 6 "Service Diagnosis" about the items of error decision.)
z
Operation by which this error is determined: The system makes a stop and the remote controller displays the
relevant "Error code".
Actuator Symbol
Electric
symbol
Operation
RTSQ8PA RTSQ10 · 12PA RTSQ14 · 16PA
Compressor 1 M1C OFF OFF OFF
Compressor 2 M2C OFF OFF
Compressor 3 M3C OFF
Outdoor unit fan1 M1F OFF OFF OFF
Outdoor unit fan2 M2F OFF
Electronic expansion valve
(Main)
EVM Y1E 0 pls
Electronic expansion valve
(Subcooling)
EVT Y3E 0 pls
Electronic expansion valve
(Refrigerant charge)
EVJ Y2E 80 pls
Solenoid valve (Refrigerant
regulator gas vent pipe)
SVG Y1S OFF
Four way valve (Heat
exchanger switch)
20SA Y3S Holds
Solenoid valve (Refrigerant
regulator liquid pipe)
SVL Y4S OFF
Solenoid valve (Hot gas) SVP Y5S OFF
Solenoid valve (Main bypass)
SVE Y6S OFF
Solenoid valve (Refrigerant
regulator discharge pipe)
SVO Y7S OFF
Solenoid valve (Refrigerant
regulator discharge pipe)
SVT Y8S OFF
Solenoid valve (Heat
exchanger hot gas)
SVHG Y9S OFF
Four way valve (High/low
pressure gas pipe switch)
20SB Y2S Holds
Ending conditions Indoor unit thermostat is turned ON.