Daikin FXSQ50P7VEB [232/370] Drain level above limit

Daikin FXZQ20M9V1B [232/370] Drain level above limit
Troubleshooting by Indication on the Remote Controller SiBE311209
223 Service Diagnosis
4.7 Drain Level above Limit
Remote
Controller
Display
AF
Applicable
Models
FXCQ, FXZQ, FXFQ, FXSQ, FXKQ, FXMQ, FXDQ, FXMQ-MA, FXUQ
Method of Error
Detection
Water leakage is detected based on float switch ON/OFF operation while the compressor is in
non-operation.
Error Decision
Conditions
When the float switch changes from ON to OFF while the compressor is in non-operation
Error code is displayed but the system operates continuously.
Supposed
Causes
Humidifier unit (optional accessory) leaking
Defective drain pipe (upward slope, etc.)
Defective indoor unit PCB
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
Modify the drain piping.
NO
YES
Check if the humidifier unit is
leaking.
Defective indoor unit PCB.
Field drain piping has a
defect such as upward
sloping.
A humidifier unit
(optional accessory) is
installed on the indoor
unit.