Daikin FXSQ50P7VEB [188/370] Image of operation in the case of a and b

Daikin FXSQ100PVE [188/370] Image of operation in the case of a and b
Field Setting SiBE311209
179 Test Operation
Image of operation in the case of A
Image of operation in the case of B
Image of operation in the case of A and B
Operation
sound
Rated operation
sound
Operation sound
of level 1
Operation sound
of level 2
Operation sound
of level 3
Approx. 55 db (target)
(The power consumption may
be increased by about 10%.)
Approx. 50 db (target)
(The power consumption may
be increased by about 20%.)
Approx. 45 db (target)
(The power consumption may
be increased by about 30%.)
Note1: Above values are reference only (measured in silent room)
Note2: Above values are for 1 module only.
Operation sound level set with "External low noise setting"
If capacity priority is set in
"Capacity priority setting", the fan
speed will be increased according
to the load of air conditioning
when load is heavier.
Operation sound during
low noise mode is
instructed can be set with
"External low noise level
setting" (Factory setting
is "Mode 2".)
Low noise mode instructing
Operation
sound
Rated
operation
sound
Operation
sound of
mode 1
Operation
sound of
mode 2
Operation
sound of
mode 3
Time set with "Low night noise
operation start setting"
If capacity priority is set in
"Capacity priority setting", the fan
speed will be increased
according to the load of air
conditioning when load is heavier.
Time set with "Low night
noise operation end setting"
Operation sound during low
night noise operation mode
is instructed can be set with
"Low night noise operation
level setting". (Factory
setting is "OFF".)
Night-time
Operation sound level set with "Low
night noise operation setting"
AM 6:00PM 8:00 PM 10:00 PM 0:00 AM 7:00 AM 8:00
Set with "Low night noise operation end setting".
(Factory setting is "AM 8:00".)
Set with "Low night noise operation start setting".
(Factory setting is "PM 10:00".)
Operation
sound
Rated
operation
sound
Operation
sound of
mode 1
Operation
sound of
mode 2
Operation
sound of
mode 3
Time set with "Low night noise
operation start setting"
Low noise mode
instructing
Operation sound set with
"External low noise setting"
PM 10:00PM 8:00 PM 0:00 AM 6:00AM 7:00 AM 8:00
Set with "Low night noise operation start setting".
(Factory setting is "PM 10:00".)
Set with "Low night noise operation end setting".
(Factory setting is "AM 8:00".)
Operation sound level set
with "Low night noise
operation setting"
Low noise
mode instructing
Operation sound set with
"External low noise setting"
Night-time
If capacity priority is set in
"Capacity priority setting", the fan
speed will be increased
according to the load of air
conditioning when load is heavier.
Time set with "Low night noise
operation end setting"
Operation sound during low noise
mode is instructed can be set with
"External quiet operation level
setting". (Factory setting is "Mode
2".)
Operation sound during low night
noise operation mode is instructed
can be set with "Low night noise
operation level setting". (Factory
setting is "OFF".)
When external low noise
instruction is received during
the operation with low night
noise operation mode.
Mode 2 precedes Mode 1 and
Mode 3 precedes Mode 2.