Daikin FXSQ50P7VEB [281/370] Troubleshooting

Daikin FXSQ40PVE [281/370] Troubleshooting
SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 272
Troubleshooting
Note:
1. Measure voltage at the X1M power supply terminal block.
2. Measure voltage at connector R · S · T pins of the diode module inside the inverter PCB while the compressor
is running.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
YES
Open phase
Normalize field cause.
Imbalance in
supplied voltage is
in excess of 14 V.
(1)
Is the voltage
imbalance applied
to the inverter in
excess of 14 V ?
(
2)
YES
NO
NO
No abnormalities are
observed in the power
supply, but the imbalance
in voltage recurs.
Power supply voltage imbalance.
Even if the power supply voltage is not
unbalanced when measuring it, there are
many cases where it gets unbalanced during
night-time (around 6:00PM to 10:00PM).
Using a device capable of
constant recording of power
supply voltage record power
supply voltage between 3
phases (L1 ~ L2, L2 ~ L3,
L3 ~ L1) for about one
continuous week.
<When voltage monitoring is possible:>
Open phase?
NO
YES
Fix power supply voltage
imbalance.
Part or wiring defect
After turning the power supply
OFF, check and repair the
main circuit wiring or parts.
(1) Loose or disconnected
wiring between power
supply and inverter
(2) K2M contact disposition,
fusion or contact is poor.
(3) Loose or disconnected
noise filter
Replace the inverter PCB.
measure
Explanation for users
In accordance with "notification of inspection results" accompanying spare parts.
Give the user a copy of "notification of inspection results" and leave
it up to him to improve the imbalance.
Be sure to explain to the user that
there is a "power supply imbalance"
for which DAIKIN is not responsible.