Daikin FXSQ50P7VEB [240/370] High pressure switch abnormality

Daikin FXSQ40PVE4 [240/370] High pressure switch abnormality
Troubleshooting by Indication on the Remote Controller SiBE311209
231 Service Diagnosis
4.15 High Pressure Switch Abnormality
Remote
Controller
Display
E3
Applicable
Models
Outdoor Unit: RTSQ8~16PAY1
Function Unit: BTSQ20PY1
Method of Error
Detection
Abnormality is detected when the contact of the high pressure protection switch opens.
Error Decision
Conditions
Error is generated when the high pressure switch activation count reaches the number specific
to the operation mode.
(Reference) Operating pressure of high pressure switch
Operating pressure: 4.0MPa
Reset pressure: 3.0MPa
Supposed
Causes
Actuation of outdoor unit high pressure switch
Defective high pressure switch
Defective outdoor unit main PCB (A1P)
Instantaneous power failure
Defective high pressure sensor
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
While in monitor mode,
check the outdoor unit and
the function unit concerned.
Check for the points shown below.
(1) Is the stop valve open?
(2) Is the high pressure switch connector properly
connected to the outdoor unit main PCB?
(3) Does the high pressure switch have continuity?
Are the three
points above
OK?
NO
YES
(1) Mount a pressure gauge on the high pressure service port.
(2) Reset the operation using the remote controller, and then restart the
operation.
Does the stop due
to error “
E3
” recur?
YES
Is the high pressure switch
operating value normal
(i.e., 4.0MPa)?
NO
NO
YES
Are the characteristics of
the high pressure sensor
normal? (1.)
NO
YES
Rectify the defective points, if
any.
Replace the high pressure switch.
Replace the high pressure sensor.
A