Troubleshooting by Indication on the Remote Controller SiBE311209
239 Service Diagnosis
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
Remove the foreign substances.
Check if any foreign
substances around
the fan.
RTSQ14 · 16PAY1 have 2 fans.
Check electric motor (electric motor 1 or 2) corresponding
to error code “
E7
” in the monitor mode of outdoor unit PCB.
Check in the monitor mode
Cut the power supply OFF and wait for 10 minutes.
{
Fan motor 1: relay connector or X1A, X2A of fan inverter
PCB.
{
Fan motor 2: relay connector or X1A, X2A of fan PCB.
Check the connection status of the connectors
Check if any
connector is
disconnected.
{
Fan motor 1: Both power supply wire and signal wire are all
white.
{
Fan motor 2: Both power supply wire and signal wire are
red in the PCB side and white in the motor side.
Check the color of relay connectors
Relay
connectors have
any connection
error.
A
Insert the connector.
Correct the connection of the relay
connectors.
YES
YES
NO
YES
NO
8HP
12HP
~
14HP
16HP
~
F1U R10
X4A
V1R
X2A
X1A
Z5C
5
X1A X2A
RDE
WHT
BLK
MS
3~
5
M1F
F1U R10
X4A
V1R
X2A
X1A
Z5C
5
X1A
X2A
RDE
WHT
BLK
MS
3~
5
M1F
F1U R10
X4A
V1R
X2A
X1A
Z9C
5
X3A
X4A
RDE
WHT
BLK
MS
3~
5
M2F
X51A X5A
X3A
X51A
RED
RED
WHT
RED
WHT

Содержание

Скачать