Troubleshooting by Indication on the Remote Controller SiBE311209
307 Service Diagnosis
Power Transistor Check
Perform the following procedures prior to check.
(1) Power OFF.
(2) Remove all the wiring connected to the PCB where power transistors are mounted on.
[Preparation]
[Point of Measurement and Judgement Criteria]
Turn OFF the power supply. Then, after a lapse of 10 minutes or more, make measurement of
resistance.
[PCB and Circuit Diagram]
CHECK 4
Multiple tester Prepare the analog type of multiple tester.
For the digital type of multiple tester, those
with diode check function are available for the
checking.
When using the analog type of multiple
tester, make measurement in resistance
measurement mode in the x1k range.
When using the digital type of multiple
tester, make measurement in diode check
mode ( )
No.
Measuring
point
Judgement
Criteria
Remarks No.
Measuring
point
Judgement
Criteria
Remarks
+– +–
1P2U
2 ~ 15k
1P2U
1.2V and
more
Due to condenser
charge and so on,
resistance
measurement may
require some time.
2P2V 2P2V
3P2W 3P2W
4UP2
15k and
more
(including )
Due to condenser
charge and so on,
resistance
measurement may
require some time.
4UP2
0.3 ~ 0.7V
5VP2 5VP2
6WP2 6WP2
7N3U 7N3U
8N3V 8N3V
9 N3W 9 N3W
10 U N3
2 ~ 15k
10 U N3
1.2V and
more
Due to condenser
charge and so on,
resistance
measurement may
require some time.
11 V N3 11 V N3
12 W N3 12 W N3
P3
UV W
N3
J1
J2
J3
P1
P1 P2
IGBT
X11A
UVW
L1
L2
L3
X10A
DM
K2
P3
N3
J1
J2
J3