Daikin FXSQ50P7VEB [252/370] Discharge pipe temperature abnormality

Daikin FXZQ25M9V1B [252/370] Discharge pipe temperature abnormality
Troubleshooting by Indication on the Remote Controller SiBE311209
243 Service Diagnosis
4.21 Discharge Pipe Temperature Abnormality
Remote
Controller
Display
F3
Applicable
Models
Outdoor Unit: RTSQ8~16PAY1
Function Unit: BTSQ20PY1
Method of Error
Detection
Abnormality is detected according to the temperature detected by the discharge pipe thermistor.
Error Decision
Conditions
When the discharge pipe temperature rises to an abnormally high level (135 °C or more)
When the discharge pipe temperature rises suddenly (120 °C or more for 10 successive
minutes)
Supposed
Causes
Defective discharge pipe temperature
Defective connection of discharge pipe thermistor
Defective outdoor unit PCB (A1P)