Daikin FXSQ50P7VEB [191/370] In setting 1 press and hold the bs1 mode for more than 5 seconds setting mode 2 is entered and h1p lights

Daikin FXSQ40PVE [191/370] In setting 1 press and hold the bs1 mode for more than 5 seconds setting mode 2 is entered and h1p lights
SiBE311209 Field Setting
Test Operation 182
(3) Detailed Setting Procedure of Low Noise Operation and Demand Control
1. Setting mode 1 (H1P OFF)
c
In setting mode 2, press the BS1 (MODE) one time. Setting mode 1 is entered and H1P OFF.
During the setting mode 1 is displayed, “In low noise operation” and “In demand control” are
displayed.
2. Setting mode 2 (H1P ON)
c
In setting 1, press and hold the BS1 (MODE) for more than 5 seconds. Setting mode 2 is
entered and H1P lights.
d
Press the BS2 (SET) several times and match the LED display with the Setting No. you
want.
e
Press the BS3 (RETURN) one time, and the present setting content is displayed.
Press the BS2 (SET) several times and match the LED display with the setting content
(as shown on next page) you want.
f
Press the BS3 (RETURN) two times. Returns to
c
.
g
Press the BS1 (MODE) one time. Returns to the setting mode 1 and turns H1P OFF.
{
: ON
z
: OFF
l
: Blink
c
de
Setting
No.
Setting
contents
Setting No. indication Setting No. indication Setting
contents
Setting contents indication (Initial setting)
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
12 External
low noise /
Demand
setting
{zzzzzz{z z { { z z
NO
(Factory
setting)
{zzzzz
l
YES
{zzzz
l
z
22 Low night
noise
operation
setting
{ z { z { { z
OFF
(Factory
setting)
{zzzzz z
Mode 1
{zzzzz
l
Mode 2
{zzzz
l
z
Mode 3
{zzzz
l l
25 External
low noise
setting
{ z { { z z {
Mode 1
{zzzz z
l
Mode 2
(Factory
setting)
{zzzz
l
z
Mode 3
{zzz
l
z z
26 Low night
noise
operation
start setting
{ z { { z { z
PM 8:00
{zzzz z
l
PM 10:00
(Factory
setting)
{zzzz
l
z
PM 0:00
{zzz
l
z z
27 Low night
noise
operation
end setting
{ z { { z { {
AM 6:00
{zzzz z
l
AM 7:00
{zzzz
l
z
AM 8:00
(Factory
setting)
{zzz
l
z z
29 Capacity
priority
setting
{ z { { { z {
Low noise
precedence
(Factory
setting)
{zzzzz
l
Capacity
priority
{zzzz
l
z
30 Demand
setting 1
{ z { { { { z
60 % of
rated power
consumption
{zzzz z
l
70 % of
rated power
consumption
(Factory
setting)
{zzzz
l
z
80 % of
rated power
consumption
{zzz
l
z z
32 Normal
demand
setting
{ z z z z z z
OFF
(Factory
setting)
{zzzzz
l
ON
{zzzz
l
z
Setting mode indication section Setting No. indication section Set contents indication section