Daikin FXSQ50P7VEB [189/370] 2 setting of demand operation by connecting the external contact input to the demand input of the external control adaptor for outdoor unit optional the power consumption of unit operation can be saved suppressing the compressor operating condition

Daikin FXSQ100PVE4 [189/370] 2 setting of demand operation by connecting the external contact input to the demand input of the external control adaptor for outdoor unit optional the power consumption of unit operation can be saved suppressing the compressor operating condition
SiBE311209 Field Setting
Test Operation 180
(2) Setting of Demand Operation
By connecting the external contact input to the demand input of the external control adaptor for
outdoor unit (optional), the power consumption of unit operation can be saved suppressing the
compressor operating condition.
A. When the demand operation is carried out by external contacts (with the use of the
external control adaptor for outdoor unit).
1. Connect the external control adaptor for outdoor unit, and short circuit terminal block (TeS1)
by the external input if necessary.
2. While in "Setting mode 2", set the setting condition for set item No. 12 (Setting of external
low noise/demand operation) to "YES".
3. If necessary, while in "Setting mode 2", select the set item No. 30 (Setting of Demand 1
level) and then set the setting condition to targeted mode.
B. When the Normal demand operation is carried out. (Use of the external control
adaptor for outdoor unit is not required.)
1. While in "Setting mode 2", make setting of the set item No. 32 (Setting of Normal demand) to
"Demand 1".
2. While in "Setting mode 2", select the set item No. 30 (Setting of Demand 1 level) and then
set the setting condition to targeted mode.
Setting content Setting method
Set item Condition Content
External control
adaptor for outdoor
unit
Outdoor unit PCB
Demand 1
Mode 1
The compressor operates at
approx. 60% or less of rating.
Short circuit "1" and
"C" on the terminal
strip (TeS1).
Set item No. 32 to "Demand 1", and item No.
30 to "Level 1".
Mode 2
The compressor operates at
approx. 70% or less of rating.
Set item No. 32 to "Demand 1", and item No.
30 to "Level 2".
Mode 3
The compressor operates at
approx. 80% or less of rating.
Set item No. 32 to "Demand 1", and item No.
30 to "Level 3".
Demand 2
The compressor operates at
approx. 40% or less of rating.
Short circuit "2" and "C".
Set item No. 32 to "Demand 2".
Demand 3 Forced thermostat OFF.
Short circuit "3" and "C".