Daikin FXSQ50P7VEB [303/370] Improper combination of indoor and outdoor units indoor units and remote controller

Daikin FXSQ25P7VEB [303/370] Improper combination of indoor and outdoor units indoor units and remote controller
SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 294
4.53 Improper Combination of Indoor and Outdoor Units,
Indoor Units and Remote Controller
Remote
Controller
Display
UA
Applicable
Models
All indoor unit models
Outdoor Unit: RTSQ8~16PAY1
Function Unit: BTSQ20PY1
Method of Error
Detection
When the model data is different between the indoor units, outdoor units and function units
When the number of indoor unit is out of the permissible range
Error Decision
Conditions
The error decision is made as soon as either of the abnormalities aforementioned is detected.
Supposed
Causes
Excess of connected indoor units
Defective outdoor unit PCB (A1P)
Mismatching of the refrigerant type of indoor and outdoor unit.
Setting of outdoor unit PCB was not conducted after replacing to spare PCB.
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check the LED lamps for
“Confirmation of error 3”
corresponding to the error
code “UA
” and for
Confirmation of error 4 in
the monitor mode.
Confirmation of
error 3
Confirmation of
error 4
Confirmation of
error 3
Confirmation of
error 4
Confirmation of
error 3
Confirmation of
error 4
Confirmation of
error 3
Confirmation of
error 4
To Diagnosis Flow 1
(Excessive number of indoor
units connected)
To Diagnosis Flow 2
(Connection of erroneous
models of indoor units)
To Diagnosis Flow 3
(Combination error of outdoor
units)
To Diagnosis Flow 4
(Wrong wiring in units dedicated
to multi connections)

Содержание

Скачать