Refrigerant Circuit SiBE311209
63 Refrigerant Circuit
FXMQ125MFV1~250MFV1
Main Control Equipment
SH control: Superheated control of heat exchanger outlet
SC control: Subcooling control of heat exchanger outlet
Thermistor
Distributor
Filter Filter
Filter
SV
Fan
M
Heat exchanger
Electronic
expansion valve
Check
valve
Solenoid
valve
Capillary
tube
Gas pipe
connection port
Liquid pipe
connection port
4D018650C
No.
Electric
Symbol
Name Main function
Y1E Electronic expansion valve
Used to control the flow rate of refrigerant, and make the SH control while
in cooling or the SC control while in heating.
Y1S Solenoid valve Used to bypass hot gas while in heating with thermostat OFF.
- Capillary tube Used to reduce pressure from high to low in bypassing hot gas.
No.
Electric
Symbol
Name Main function
R1T
Suction air temperature
thermistor
Used to turn ON or OFF the thermostat and select cooling or heating
operation.
R2T
Liquid pipe temperature
thermistor
Used to control the opening degree of EV (Y1F) under the SC control.
R3T
Gas pipe temperature
thermistor
Used to control the opening degree of EV (Y1E) under the SH control.
R4T
Discharge air temperature
thermistor
Used to control the electronic expansion valve opening and thermostat ON/
OFF so as to keep the discharge air temperature at the set temperature.