Daikin RWEYQ30PY1 Сервис мануал онлайн [139/342] 549197

Daikin RWEYQ30PY1 Сервис мануал онлайн [139/342] 549197
Field Setting Si30-813
128 Test Operation
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
Factory set
1
Cool / Heat
Unified address
khhhhhk
Address 0
khhhhhh
Binary number 1
khhhhhk
(6 digits) ~
31
khkkkkk
2
Low noise/demand
address
khhhhkh
Address 0
khhhhhh
Binary number 1
khhhhhk
(6 digits) ~
31
khkkkkk
4
Number of units for
sequential starting
khhhkhh
1 unit
khhhhhk
2 units
khhhhkh
3 units
khhhhkk
5
Indoor forced fan H
khhhkhk
Normal operation
khhhhhk
Indoor forced fan H
khhhhkh
6
Indoor forced
operation
khhhkkh
Normal operation
khhhhhk
Indoor forced operation
khhhhkh
8
Te setting
khhkhhh
Low (Level L)
khhhhhk
Normal (Level M)
khhhhkh
High
khhhhkk
High
khhhkhh
High
(Level H)
khhhkhk
High
khhhkkh
High
khhhkkk
9
Tc setting
khhkhhk
Low
khhhhhk
Normal (factory setting)
khhhhkh
High
khhhkhh
12
External low noise/
demand setting
khhkkhh
External low noise/demand:
NO
khhhhhk
External low noise/demand:
YES
khhhhkh
13
Airnet address
khhkkhk
Address 0
khhhhhh
Binary number 1
khhhhhk
(6 digits) ~
63
khkkkkk
20
Additional refrigerant
operation setting
khkhkhh
Refrigerant charging: OFF
khhhhhk
Refrigerant charging: ON
khhhhkh
21
Refrigerant recovery
mode setting
khkhkhk
Refrigerant recovery: OFF
khhhhhk
Refrigerant recovery: ON
khhhhkh
26
Interlock abnormal
display setting
khkkhkh
OFF
khhhhhk
ON
khhhhkh

Содержание