Daikin RWEYQ30PY1 [94/342] Oil return operation in heating or cooling heating simultaneous operation

Daikin RWEYQ30PY1 [94/342] Oil return operation in heating or cooling heating simultaneous operation
Si30-813 Special Operation
Function 83
7.1.2 Oil Return Operation in Heating or Cooling/Heating simultaneous
Operation
[Starting conditions]
Start oil return operation in heating operation referring to the following conditions.
Cumulative compressor operating time after power supply turns on exceeds 2 hours and the
time after the completion of previous oil return operation exceeds 8 hours. And cumulative oil
return is calculated based on Tc, Te compressor load.
Heating & Cooling/heating simultaneous operation oil return
Compressor (M1C) 74 Hz
SVG (Y4S) OFF
Same as normal
heating operation
Indoor unit control
Ending condition 2 min. Max.8 min.
Max.3 min.
Indoor heating unit
expansion valve
EV (Y1E) Normal control320 pulse
EV1 (Y1E)
20S2=OFF : 2000 pulse
20S2=ON : 180 pulse
Sub-cooling
electronic
expansion valave
EV3 (Y3E) 0 pulse
Main heat
exchanger
electronic
expansion valve
104 Hz
4 way valve 1 20S1 (Y5S) ON
4 way valve 2 20S2 (Y7S) Heat exchanger mode
SVP (Y1S) ON
SVE (Y2S) OFF
SVL (Y3S) OFF
EV (Y1E) 320 pulse Normal control
Indoor cooling unit
expansion valve
Indoor heating unit
fan
(M1,2F)
OFF
Receiver gas
discharge solenoid
valve
Liquid pipe stop
solenoid valve
(M1,2F) Normal control
Indoor cooling unit
fan
SVSL (Y6S)
ON
2000 pulse
0 pulse
OFF
OFF
ON
OFF
OFF
OFF
ON
Thermostat off :
Thermostat on/Stop :
Indoor unit control
OFF
Hot gas bypass
solenoid valve
Water heat exch.
oil return solenoid
valve
Receiver gas
charging solenoid
valve
Parts name
Preperation
Electrical
symbol
After oil return
operation
During oil return
operation
Symbol