Daikin RWEYQ30PY1 [237/342] Power supply insufficient or instantaneous failure

Daikin RWEYQ30PY1 [237/342] Power supply insufficient or instantaneous failure
Troubleshooting by Indication on the Remote Controller Si30-813
226 Troubleshooting
2.41
U2
Power Supply Insufficient or Instantaneous Failure
Remote
Controller
Display
U2
Applicable
Models
Outside unit
RWEYQ8P, 10P
Method of
Malfunction
Detection
Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction
Decision
Conditions
When the capacitor above only has a voltage of 360 V or less (YL) and 210V or less (TL).
Supposed
Causes
Power supply insufficient
Instantaneous failure
Open phase
Defect of inverter PC board
Defect of outside control PC board
Defect of K1M.
Main circuit wiring defect