Special Operation Si30-813
84 Function
7.2 Oil Return Operation of Water Heat Exchanger
[Oil return operation of Water heat exchanger]
When the water heat exchanger is used as evaporator during heating or simultaneous cooling/
heating operation, the operation that the oil accumulated in the water heat exchanger is
returned to compressor is conducted.
[IN condition]
After a certain continuous period of time has passed under the following conditions, oil return
operation starts.
20S2 = 1 (Water heat exchanger is an evaporator.)
&
Tg – Te > 10
°
C
Elapse of a certain period of time
Water heat exchanger oil return control
Parts name
Symbol
Electrical
symbol
Water heat exchanger oil return control
Compressor (M1C)
20S1 (Y5S)
20S2 (Y7S)
52 Hz
ON
OFF
EV1 (Y1E)
EV3 (Y3E)
SVP (Y1S)
SVE (Y2S)
SVL (Y3S)
SVG (Y4S)
SVSL (Y6S)
(M1,2F)
EV (Y1E)
Receiver gas
charging solenoid
EV (Y1E)
Indoor heating unit
expansion valve
Receiver gas
discharge solenoid
valve
Non-operation unit
liquid pipe stop
solenoid valve
Indoor cooling unit
fan
Indoor cooling unit
expansion valve
(M1,2F)
Indoor heating unit
fan
Hot gas bypass
solenoid valve
Water heat exch. oil
return solenoid valve
Main heat exchanger
electronic expansion
valve
180 pulse
OFF
ON
OFF
ON
ON
300 pulse
Sub-cooling
electronic expansion
valve
Tharmostat on : Normal control
Tharmostat off/Stop : 500 pulse
Ending condition Max.90 sec.
Normal control
4 way valve (Main)
4 way valve
(for heat exchanger)