2–44 Part 2 – Functional Description
3
1
2
4
5
2.4.7 Manufacturer Menu
Operational
information
Using this menu you can set all manufacturer data. Password is required to enter this menu. The
parameters can only be modified by trained individuals.
Warning : Improper setpoints or values can cause erratic chiller operation and damage to the
chiller. Please use caution whenever changing setpoints or values.
Expansion valve
type
This screen allows you to select the expansion valve type.
Economizer setting This function is only used on EWAD-BJYNN/A and EWAD-BJYNN/Z.
This screen allows you to enable/disable the economizer.
P When N is selected, the economizer function is disabled. (EWAD-BJYNN and EWAD-BJYNN/Q)
P When Y is selected, the economizer function is enabled. (EWAD-BJYNN/A and EWAD-BJYNN/Z)
P When En. Economizer Y is selected, line 3 and line 4 will appear.
P Economizer on : economizer activation point
P Economizer off : economizer switch off point
Key :
+
Password :
Switching between
control board # 1 and # 2 :
blue
Possible settings :
P Electronic
P Thermostatic (not used)
Expansion Valve
Electronic Gas Type – – – –
En. Economizer N/Y
Economizer On 090 %
Economizer Off 075 %