1.17 Electrical Specifications: EWAD-BJYNN/Z
Electrical
specifications
The table below contains the electrical specifications
Notes:
(1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current is based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current is based on: 14/9 °C entering/leaving evaporator water temperature and 40°C ambient temp.
(4) Inrush current of biggest compressor + 75 % of nominal absorbed current of the other compressor + fans
current.
(5) Compressor FLA + fans current.
Model EWAD-BJYNN/Z
Unit size 600 650 700 850 900 950 C10
Standard voltage (1) 400 V - 3ph - 50 Hz
Nominal unit current (2) A 392 420 444 585 604 636 652
Max compressor current (3) A 416 447 474 618 640 678 705
Fans current A 12 13 14 18 20 20 22
Max unit current (3) A 428 460 488 636 660 698 727
Max unit inrush current (4) A 790 791 812 943 945 965 986
Max unit current for wires sizing (5) A 458 507 556 687 737 785 835