ESIE07-04 Checking the Inputs and Outputs
Part 3 – Troubleshooting 3–9
33
4
5
1
2.3 List of Analog Inputs
The table below gives an overview of all the analog inputs.
N BOARD # 1 BOARD # 2
B1 Oil pressure # 1 Oil pressure # 3
B2 Oil pressure # 2 Oil pressure # 4
B3 Setpoint Override ---
B4 Gas temperature on compressor
discharge # 1
Gas temperature on compressor
discharge # 3
B5 Gas temperature on compressor
discharge # 2
Gas temperature on compressor
discharge # 4
B6 Gas pressure on compressor discharge
# 1
Gas pressure on compressor discharge
# 3
B7 Gas pressure on compressor discharge
# 2
Gas pressure on compressor discharge
# 4
B8 Demand limit/Current limit ---
B9 In water Temperature (common on 2
Evap unit)
In water Temperature (common on 2
Evap unit)
B10 Evaporator Out water Temperature
(Common on 2 Evap unit)
Evaporator Out water Temperature
(Common on 2 Evap unit)