Daikin EWAD900BJYNN/A [204/346] Maintenance input menu

Daikin EWAD900BJYNN/A [204/346] Maintenance input menu
The Digital Controller ESIE07-04
2–64 Part 2 – Functional Description
3
1
2
4
5
2.4.10 Maintenance Input Menu
Operational
information
Using this menu you can set all maintenance parameters. The parameters can only be modified only
by trained individuals.
Evaporator pump
timers
This screen allows you to settle the evaporator threshold (maintenance) and running hours.
Compressor
running data
setting
This screen allows you to set the compressor threshold (maintenance) and running hours.
Screen : Digit
maintenance password
Password :
Switching between
control board # 1 and # 2 :
Yellow blue
P Threshold : Running hour when unit will show “Evaporator Pump Maintenance” Alarm
P Reset Y : Reset evaporator pump hours
P Adjust : Enter the running hours of the pump. This has to be done whenever software or
controller is changed.
Evap. Pump h. Count.
Threshold 010 x 1000
Reset N
Adjust 000000
P C : 1 : Compressor information of compressor circuit 1
P Threshold : Running hour of this compressor when unit shows “Compressor # 1 Maintenance”
alarm
P Reset Y : Reset compressor running hours
P Adjust : Enter the running hours of this compressor. This has to be done whenever soft-
ware or controller is changed.
Comp. h. Count C : 1
Threshold 010 x 1000
Reset N
Adjust 000000