Daikin RXYQ34PY1 [127/398] Stopping operation

Daikin RXYQ10PY1 [127/398] Stopping operation
Special Control Si34-601A
116 Function
3.7 Stopping Operation
3.7.1 When System is in Stop Mode (Normal operation stop)
This mode is used to define actuator operations when the system stops.
* Actuators are based on RXYQ14~18P.
3.7.2 Stop due to Malfunction
In order to protect compressors, if any of the following items has an abnormal value, the system will make "stop with
thermostat OFF" and the malfunction will be determined according to the number of retry times.
Actuator Operation
Compressor OFF
Outdoor unit fan OFF
Four way valve Holds
Main motorized valve (EV1) 0 pls
Subcooling motorized valve (EV2) 0 pls
Hot gas bypass valve (SVP) OFF
Accumulator oil return valve (SVO) OFF
Injection (SVT) (RXYQ5P model only) OFF
Ending conditions Indoor unit thermostat is turned ON.
Item Judgment Criteria Malfunction Code
1. Abnormal low pressure level 0.07MPa E4
2. Abnormal high pressure level 4.0MPa E3
3. Abnormal discharge pipe temperature level 135°CF3
4. Abnormal power supply voltage Reverse-phase power supply U1
5. Abnormal inverter current level 16.1A: 260 sec. L8
6. Abnormal radiator fin temperature level 93°CL4