Daikin RXYQ34PY1 [257/398] E9 outdoor unit malfunction of moving part of electronic expansion valve y1e y2e

Daikin RXYQ34PY1 [257/398] E9 outdoor unit malfunction of moving part of electronic expansion valve y1e y2e
Troubleshooting by Indication on the Remote Controller Si34-601A
246 Troubleshooting
3.19
E9
Outdoor Unit: Malfunction of Moving Part of
Electronic Expansion Valve (Y1E, Y2E)
Remote
Controller
Display
E9
Applicable
Models
RXYQ5P~54PY1
Method of
Malfunction
Detection
Check disconnection of connector
Check continuity of expansion valve coil
Malfunction
Decision
Conditions
Error is generated under no common power supply when the power is on.
Supposed
Causes
Defect of moving part of electronic expansion valve
Defect of outdoor unit PC board (A1P)
Defect of connecting cable