Daikin RXYQ34PY1 [251/398] E5 outdoor unit inverter compressor motor lock

Daikin RXYQ34PHY1 [251/398] E5 outdoor unit inverter compressor motor lock
Troubleshooting by Indication on the Remote Controller Si34-601A
240 Troubleshooting
3.16
E5
Outdoor Unit: Inverter Compressor Motor Lock
Remote
Controller
Display
E5
Applicable
Models
RXYQ5P~54P
Method of
Malfunction
Detection
Inverter PC board takes the position signal from UVW line connected between the inverter and
compressor, and the malfunction is detected when any abnormality is observed in the phase-
current waveform.
Malfunction
Decision
Conditions
This malfunction will be output when the inverter compressor motor does not start up even in
forced startup mode.
Supposed
Causes
Inverter compressor lock
High differential pressure (0.5MPa or more)
Incorrect UVW wiring
Faulty inverter PC board
Stop valve is left in closed.