1.2.6 Test Run
1.2.6.1 Before Test Run
Make sure the following works are completed in accordance with the installation manual.
Piping work
Wiring work
Air tight test
Vacuum drying
Additional refrigerant charge
Check that all work for the indoor unit are finished and there are no danger to operate.
1.2.6.2 Test Run
After check operation is completed, operate the unit normally and check the following.
(1) Make sure the indoor and outdoor units are operating normally.
(2) Operate each indoor unit one by one and make sure the corresponding outdoor unit is also
operating.
(3) Check to see if cold (or hot) air is coming out from the indoor unit.
(4) Push the fan direction and strength buttons on the remote controller to see if they operate
properly.
NOTE:
Heating is not possible if the outdoor temperature is 24°C or higher. Refer to the Operation
manual.
If a knocking sound can be heard in the liquid compression of the compressor, stop the unit
immediately and then energize the crank case heater for a sufficient length of time before
restarting the operation.
Once stopping, the compressor will not restart in about 5 minutes even if the On/Off button of
the remote controller is pushed.
When the system operation is stopped by the remote controller, the outdoor units may
continue operating for further 5 minutes at maximum.
The outdoor unit fan may rotate at low speeds if the Night-time low noise setting or the
External low noise level setting is made, but this is not a malfunction.