Daikin RXYQ34PY1 [148/398] List of swing flap operations

Daikin RXYQ44PHY1 [148/398] List of swing flap operations
Si34-601A Outline of Control (Indoor Unit)
Function 137
(2) The heater control (ON/OFF)
is conducted by converting
the heater temperature into
the condensing pressure
equivalent saturated
temperature (Tc) according
to the temperature detection
through the high pressure sensor (SINPH) of the outdoor unit.
[Fan residual operation]
While the heater turns OFF, in order to prevent the activation of the thermal protector, the fan
conducts residual operation for a given period of time after the heater turns OFF. (This
operation is conducted regardless of with or without heater equipped.)
Residual operation time = 100 seconds on ceiling suspended type or 60 seconds on other types
6.10 List of Swing Flap Operations
Swing flaps operate as shown in table below.
*1. L or LL only on FXFQ models
ON 50ºC 60ºC
OFF
Condensing pressure
equivalent saturated
temperature
Fan
Flap
FXFQ
FXCQ
FXHQ
FXKQ
FXAQ
Heating
Hot start from defrosting
operation
Swing OFF Horizontal Horizontal Horizontal
Wind direction set OFF Horizontal Horizontal Horizontal
Defrosting operation
Swing OFF Horizontal Horizontal Horizontal
Wind direction set OFF Horizontal Horizontal Horizontal
Thermostat OFF
Swing LL Horizontal Horizontal Horizontal
Wind direction set LL Horizontal Horizontal Horizontal
Hot start from thermostat
OFF mode (for prevention
of cold air)
Swing LL Horizontal Horizontal Horizontal
Wind direction set LL Horizontal Horizontal Horizontal
Stop
Swing OFF Horizontal Horizontal Totally closed
Wind direction set OFF Horizontal Horizontal Totally closed
Cooling
Thermostat ON in dry
operation using micro
computer
Swing L*
1
Swing Swing Swing
Wind direction set L*
1
Set Set Set
Thermostat OFF in dry
operation using micro
computer
Swing
OFF or L
Swing Swing Swing
Wind direction set Set Set Set
Thermostat OFF in
cooling
Swing Set Swing Swing Swing
Wind direction set Set Set Set Set
Stop
Swing OFF Horizontal Horizontal Totally closed
Wind direction set OFF Set Horizontal Totally closed
Micro computer control
(including cooling
operation)
Swing L Swing Swing Swing
Wind direction set L Set Set Set

Содержание