Daikin EWYQ130DAYN [263/524] Free cooling _

Daikin EWAQ130DAYN [263/524] Free cooling _
ESIE06-05 The Digital Controller For Multiscroll Chillers
Part 2 – Functional Description 2–37
3
2
4
5
1
Free Cooling
Chang. Dig. Inp.
This screen allows modification of the free cooling based on a digital input signal.
Settings:
2.8.9 DICN
DICN This screen allows modifications of the DICN function.
This menu can only be entered when MS is selected in the service/DICN menu.
MODE : CHANG.DIG.INP., free cooling based on a changeable digital input signal
(example from an external thermostat)
PUMP : Define if pump is ON/OFF during free cooling operation
LEAD : Lead time of the evaporator water pump
FREE COOLING_
MODE:CHANG.DIG.INP
PUMP:ON LEAD:000s
MASTER SETTINGS_
MODE:NORMAL
OFFSET:0000h
PUMP ON IF:UNIT ON
SLAVE SETTINGS
MODE:NORMAL
OFFSET:0000h
PUMP ON IF:UNIT ON
_
OR