The Digital Controller For Multiscroll Chillers ESIE06-05
2–66 Part 2 – Functional Description
3
1
2
4
5
Fan Control This screen allows modification of the fan high pressure setpoints.
Settings:
Fan Control Anti-
hunting
This screen allows modification of the anti-hunting timer and reset conditions.
Settings:
FANST. B3 : High pressure setpoint for fan control
-First value: setpoint used for standard ON/OFF fans and units
with inverter fans
-Second value: setpoint used for inverter fans working in LOW
NOISE mode
UNLOAD CONST : Parameter used to calculate the high pressure fan switching point
if 1 compressor of this circuit is in operation.
COMPAR. PRESSURE : Parameter to specify extra condition for fan up/down.
_^
FANST. B3:35.0b/37.0b
UNLOAD CONST:02.6b
COMPAR. PRESSURE:01.9b
FAN CONTROL
HUNTING PR TIME : When a fanstep changes with ± 1 fanstep and it becomes the
same fanstep within HUNTING PR TIME, then the anti-hunting
function will be enabled.
- ON/OFF fans: 720s
- Inv. fans: 240s
RESET CONDITION
TEMP
: When outlet water temp. rises with 2°C, the anti-hunting function
will be reset.
RESET CONDITION
AMBIENT
: When the ambient temp. rises with 3°C, the anti-hunting function
will be reset.
_
HUNTING PR TIM:0720s
RESET CONDTEMP:02.0 °C
RESET CONDAMB.:03.0 °C
FAN CONTROL