Daikin EWYQ130DAYN [393/524] Automatic defrost

Daikin EWYQ180DAYN [393/524] Automatic defrost
ESIE06-05 Functional Control for a Standalone Unit
Part 2 – Functional Description 2–167
3
2
4
5
1
3.22.3 Automatic defrost
Defrost forbidden
timer
Defrost forbidden timer.
This is the minimum time between 2 defrost cycles in order to keep the heating capacity and to prevent
frequent defrosting.
The timer can be
- Normal startvalue (def 30 min, range 20 - 120 min).
- Short start value (default 10 min, range 1 - 20 min).
If timer is not on 0, the defrost cycle cannot be started.
The timer starts counting from previous defrost finished.
In case of a safety stop, the timer starts counting.
In case of thermostat-OFF, counter does not reset and keeps on counting.
If during countdown of the timer, timer selection is modified from normal to short, and the already
time past is larger than the short timer value ==> timer is put on 0.
Defrost start
conditions
A = “start const temp”, default 12 °C (can be changed between 5 - 25°C).
Ta = ambient temperature sensor
Tr = coil sensor
(in case of EWYQ230/250 : lowest temperature of 2 coil temperature sensors = Tr)
During compressor operation, above conditions should be met for 5 min before defrost will start. If less
than 5 minutes, re-detect again.
AND
OR
Defrost forbidden timer T(min) must be zero
Conditions were met at time
of coil sensor failure
1) Ta-Tr> 0.4 x Ta+A
2) Tr < 0°C
3) Ta < 10 °C