Daikin EWYQ130DAYN [315/524] A 04 c b 03 c b 00 c

Daikin EWYQ130DAYN [315/524] A 04 c b 03 c b 00 c
ESIE06-05 The Digital Controller For Multiscroll Chillers
Part 2 – Functional Description 2–89
3
2
4
5
1
Master Settings This screen allows modification of the master unit settings.
Settings:
DICN Thermostat This screen allows modification of the DICN thermostat settings.
Step length settings:
Remark: DICN thermostat control is only possible on Inlet control.
PRIORITY: 0-2 : Select Unit priority - stepL Priority
STEPLENGHTTH: 1,5° : parameter used in the formula to calculate the loading priority
STANDBY IF MAX CAP : N: When all “normal” units are at maximum capacity
standby unit will start up to reach the setpoint.
Y: When all “normal” units are at maximum capacity
standby unit will not start up (only on error on other units)
_
PRIORITY:0-2
MASTER SETTING
STEPLENGTH:1.5 °C
STANDBY IF MAX CAP:Y
A:Step difference value A, used for the DICN thermostat function
B:Step difference value B, used for the DICN thermostat function
C:Step difference value C, used for the DICN thermostat function
_^
STEPLENGTH
DICN THERMOSTAT
A:04.0 °C B:03.6 °C B:00.4 °C