ESIE06-05 Functional Control for a Standalone Unit
Part 2 – Functional Description 2–133
3
2
4
5
1
3.10 Free Cooling
Introduction When ambient temperature is low, cool water can be made easily by direct heat exchange with
ambient air. Free cooling can work on ambient or difference between inlet water temperature and
ambient temperature.
When free cooling is activated a 3 way valve will be closed.
Free cooling can only be used if the changeable digital output "free cooling" is selected in the service
Input/Output menu.
Free cooling function is only active if unit is on.
It is possible to work with indirect or direct free cooling on ambient temperature.
With indirect free cooling the water of the load circulates through a separate heat exchanger instead
of through the chiller. A second water circuit circulates through the other side of that heat exchanger.
In direct free cooling it is the water from the load that is directly cooled by the ambient air.