ESIE06-05 The Digital Controller For Multiscroll Chillers
Part 2 – Functional Description 2–93
3
2
4
5
1
Warning Settings This screen allows modification of the setting if during the high pressure set back function or the
compressor protection function, a warning has to be displayed.
Settings:
High Discharge
Safety Settings
This screen allows modification of the high discharge temperature setpoint.
Settings:
IF HP SETBACK:
N: If the unit is in the HP setback function, no warning will be displayed
Y: If the unit is in the HP setback function, a warning will be displayed
IF COMPR PR:
N: If the unit is in the compressor protection function, no warning will be displayed.
Y: If the unit is in the compressor protection function, a warning will be displayed.
_ WARNING
IF HP SETBACK:N
IF COMPR PR:N
HIGH DIS. SAFETY : When the discharge temperature of a compressor rises above
the setpoint, the circuit will shut down and a HIGH
DISCHARGE TEMP. ERROR will be displayed.
_ SAFETY
HIGH DIS.SAFETY:135 °C