Inverter heat pump RXYQ5M7W1B, RXYQ8,10M8W1B
18
6
Systems Outdoor Units
168
6 Dimensions
6-5 Foundation drawing
RXYQ-M
3D040102B
929
729
100
100
50
100 50
160 160AA
50
Floor
A
B
X
Drain ditch
Drain ditch
(Smooth down grade of about 1/50)
Foundation bolt type: JA
3 thread ridges
Nut
Spring washer
Frame
Foundation bolt executing method
When installing multiple units in connetion
Size M12
Four bolts are required
When building a
foundation on the
concrete floor
When building a
foundation on the
ground
Y groove
Except 5HP models
ø 100
80
80
80
60
Y
groove
Y
groove
X - X cross section
75
NOTES
1 The proportions of cement, sand, gravel for concrete shall be 1:2:4 and the reinforcement bars,
with diameter 10mm, (approx. 300mm intervals) shall be placed.
2 The surface has to be finished with mortar, The corner edges have to be chamfered.
3 When the foundation is built on a concrete floor, rubble is not necessary. However, the surface
of the section on witch the foundation is built has to have rough finish.
4 A drain ditch has to be made around the foundation to thoroughly drain water from the
equipment installation area.
5 When installing the equipment on a roof, the floor strength has to be checked, and waterproofing
measures have to be taken.
6 Y groove unnecessary for 5HP models.
Model A B
5HP 497 697
8HP
10HP
792 992
12HP
14HP
16HP
1,102 1,302