Daikin RXYQ16M7W1B [19/182] Specifications

Daikin RXYQ8M7W1B [19/182] Specifications
Inverter heat pump RXYQ5M7W1B, RXYQ8,10M8W1B
18
1
Systems Outdoor Units
18
1 Specifications
1-3 Electrical specification
1-3-5 34~48HP
RXYQ-M8W1B 34 36 38 40 42 44 46 48
POWER SUPPLY Name W1 W1 W1 W1 W1 W1 W1 W1
Phase 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~
Frequency Hz5050505050505050
Voltage V 400 400 400 400 400 400 400 400
CURRENT Nominal running
current (RLA)
Cooling A 49.40 51.30 53.40 59.00 60.90 57.10 68.60 70.50
Heating A 48.20 49.80 51.70 54.90 56.70 53.00 61.70 63.30
Starting current (MSC) A 123.00 125.00 126.00 135.00 137.00 138.00 147.00 148.00
Minimum circuit amps (MCA) A 79.00 79.00 79.50 89.60 89.60 90.10 100.20 100.20
Maximum fuse amps (MFA) A 100 100 100 125 125 125 125 125
Total overcurrent amps (TOCA) A 96.90 96.90 97.50 110.50 110.50 110.00 124.00 124.00
Full load amps (FLA) A 2.5 (fan motor) 2.5 (fan motor) 2.9 (fan motor) 2.9 (fan motor) 2.9 (fan motor) 3,3 (fan motor) 3,3 (fan motor) 3,3 (fan motor)
VOLTAGE RANGE Minimum V 360 360 360 360 360 360 360 360
Maximum V 440 440 440 440 440 440 440 440
WIRING CONNECTIONSFor power supplyQuantity 55555555
Remark Earth wire included
For connection
with indoor
Quantity 22222222
Remark P1-P2 P1-P2 P1-P2 P1-P2 P1-P2 P1-P2 P1-P2 P1-P2
POWER SUPPLY INTAKE Both indoor and outdoor unit
3TW25801-4A
NOTES
1 MCA = 1.25 x maximum RLA + other RLA + EA FLA
2MCA/MFA:
MCA/MFA: MCA = 1.25 x maximum RLA + other RLA + EA FLA, MFA is
smaller than or equal to 2.25 x maximum RLA + other RLA + EA FLA, next
lower standard fuse rating minimum 16A
MFA is smaller than or equal to 2.25 x maximum RLA + other RLA + EA
FLA
MFA is used to select the circuit breaker and the ground fault circuit
interrupter (earth leakage circuit breaker)
3 MSC means the maximum current during start up of the compressor
Maximum allowable voltage range variation between phases is 2%
Next lower standard fuse rating minimum 16A
4 RLA is based on following conditions :
indoor temperature : 27°CDB/19°CWB ,
outdoor temperature: 35°CDB
Select wire size based on the value of MCA or TOCA
5 TOCA means the total value of each OC set
6 Voltage range: units are suitable for use on electrical systems where
voltage supplied to unit terminal is not below or above listed range limits
7 For more details concerning conditional connections, see
http://www.daikineurope.com/extranet, select "Daikin Documentation"
and select "conditional connection", "the requested product type" and
"English" from the drop down lists, click the search button.
Finally, click on the document title of your choice.