ED34-645B Control Devices
Control 769
16
4.5.6 Setting Group No. for Centralized Control
In order to conduct the central remote control using the central remote controller and the unified ON/OFF controller,
Group No. settings should be made by group using the operating remote controller.
Make Group No. settings for central remote control using the operating remote controller.
1. While in normal mode, press and hold the
switch for a period of four seconds or more to set
the system to "Field Setting Mode".
2. Select the MODE No. “00” with the “ ” button.
3. Use the “ ” button to select the group No. for
each group.
(Group numbers increase in the order of 1-00, 1-
01, ... 1-15, 2-00, ... 4-15.)
4. Press “ ” to set the selected group No.
5. Press “ ” to return to the NORMAL MODE.
Note:
For simplified remote controller, see the installation table.
For setting group No. of HRV and wiring adaptor for other air conditioners, etc., refer to the instruction manual
attached.
NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table. Be sure to keep the
installation table with the operation manual for maintenance.
4.5.7 Error Diagnosing Function
This schedule timer is provided with the malfunction diagnosing function. The malfunction code flashes if there
occurs any malfunction in communication, etc. between and among the optional controllers for centralized control. In
addition, the operation lamp also flashes if there occurs any malfunction in communication with the indoor unit. Check
the contents of the display and contact your DAIKIN dealer because the signals give you the idea of the trouble area.
SETTING
TEST
UNIT NO.
5
2,6
4
3
GROUP NO.
MODE NO.
FIELD SET
MODE