Function and Control 103
3.1.2 Cooling Only Model
A Outdoor Heat
Exchanger
Thermistor (DCB)
1. The outdoor heat exchanger thermistor is used for controlling target discharge temperature.
Set a target discharge temperature depending on the outdoor and indoor heat exchanger
temperature.
Control the electronic expansion valve opening so that the target discharge temperature can
be obtained.
2. When cooling: an outdoor heat exchanger thermistor is used for detecting the discharge
thermistor disconnected.
When the temperature of the discharge piping is lower than the temperature of outdoor heat
exchanger, a disconnected discharge thermistor can be detected.
3. The outdoor heat exchanger thermistor is used for high pressure protection during cooling
operation.
B Discharge
Pipe Thermistor
(DOT)
1. The discharge pipe thermistor is used to control the discharge pipe.
If the temperature of discharge pipe (used in place of the inner temperature of the
compressor) rises abnormally, the operating frequency drops or the operation must be
halted.
2. The discharge pipe thermistor is used for detecting the discharge thermistor disconnected.
A
B
Compressor
(R3078)
Electronic
expansion valve