Daikin RP71B7V1 [10/48] Specifications

Daikin RP100B7V1 [10/48] Specifications
ELECTRICAL DATA
RP100B7V1/W1/T1
Unit combination Power supply Compressor OFM IFM
Indoor unit Outdoor unit Hz - Volts Voltage range MCA TOCA MFA LRA RLA kW FLA kW FLA
FHYCP100/FUYP100 RP100B7V1 50-230
Max. 50Hz-253C
Min. 50Hz-197V
24.8 35.7 40 96.9 17.8
0.08
+
0.085
0.84
+
0.7
0.09 1.0
FHP100 RP100B7V1 50-230 24.7 35.4 40 96.9 17.8
0.08
+
0.085
0.84
+
0.7
0.13 0.9
FHYP100 RP100B7V1 50-230 24.5 35.6 40 96.9 17.6
0.08
+
0.085
0.84
+
0.7
0.13 0.7
FHYBP100 RP100B7V1 50-230 24.8 35.7 40 96.9 17.8
0.08
+
0.085
0.84
+
0.7
0.135 1.0
FAYP100 RP100B7V1 50-230 24.2 35.3 40 96.9 17.8
0.08
+
0.085
0.84
+
0.7
0.049 0.4
Unit combination Power supply Compressor OFM IFM
Indoor unit Outdoor unit Hz - Volts Voltage range MCA TOCA MFA LRA RLA kW FLA kW FLA
FHYCP100/FUYP100 RP100B7W1 50-400/230
Max. 50Hz-440/253V
Min. 50Hz-360/197V
10.7 13.2 16 45.5 6.5
0.08
+
0.085
0.84
+
0.7
0.09 1.0
FHYP100 RP100B7W1 50-400/230 10.4 13.1 16 45.5 6.5
0.08
+
0.085
0.84
+
0.7
0.13 0.7
FHYBP100 RP100B7W1 50-400/230 10.7 13.2 16 45.5 6.5
0.08
+
0.085
0.84
+
0.7
0.135 1.0
FAYP100 RP100B7W1 50-400/230 10.1 12.6 16 45.5 6.5
0.08
+
0.085
0.84
+
0.7
0.049 0.4
Unit combination Power supply Compressor OFM IFM
Indoor unit Outdoor unit Hz - Volts Voltage range MCA TOCA MFA LRA RLA kW FLA kW FLA
FHYCP100/FUYP100 RP100B7T1 50-230
Max. 50Hz-264V
Min. 50Hz-198V
16.2 24.5 32 75.4 10.9
0.08
+
0.085
0.84
+
0.7
0.09 1.0
FHYP100 RP100B7T1 50-230 15.9 24.4 32 75.4 10.9
0.08
+
0.085
0.84
+
0.7
0.13 0.7
FHYBP100 RP100B7T1 50-230 16.2 24.5 32 75.4 10.9
0.08
+
0.085
0.84
+
0.7
0.135 1.0
FAYP100 RP100B7T1 50-230 15.6 23.9 32 75.4 10.9
0.08
+
0.085
0.84
+
0.7
0.049 0.4
3TW23229-2A
SYMBOLS
MCA : Min. Circuit Amps
TOCA : Total Over Current Amps
MFA : Max. Fuse Amps (see note 7)
LRA : Locked Rotor Amps
RLA : Rated Load Amps (A)
OFM : Outdoor Fan Motor
IFM : Indoor Fan Motor
FLA : Full Load Amps
kW : Rated motor output
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. TOCA means the total value of each OC set
3. Voltage range
Units are suitable for use on electrical systems where
voltage supplied to unit terminals is not below or above
listed operation range limits
4. Maximum allowable voltage unbalance between phases is
2%
5. MCA/MFA
MCA = 1.25 x RLA + ea. FLA
MFA 2.25 x RLAA + ea. FLA
(next lower standard fuse rating, min.15A)
6. Select wire size based on the larger value of MCA or TOCA
7. Instead of fuse, use circuit breaker
Pair Application R-407C R25-60GZ7RP71-250B7
2
Specifications
13
2
8
Split - Sky Air Outdoor Units