Daikin RP71B7V1 [7/48] Specifications

Daikin RP71B7T1 [7/48] Specifications
ELECTRICAL SPECIFICATIONS
OUTDOOR UNITS R25GZ7V11 R35GZ7V11
R45GZ7V11/W11
R60GZ7W1
RP71B7V1/W1/T1
CURRENT Nominal running
current
cooling
A 3.8 6.4 10.8/3.98 5.6/6.35 -
Maximum running
current
cooling
A---26-
Starting current
cooling
A 20 33.5 48/19 26 -
OUTDOOR UNITS R25GZ7V11 R35GZ7V11
R45GZ7V11/W11
R60GZ7W1
RP71B7V1/W1/T1
POWER SUPPLY V11 V11 V11/W11 W1 V1/W1/T1
NOMINAL
DISTRIBUTION
SYSTEM VOLTAGE
Phase 1 1 1/3N 3N 1/3N/3
Frequency Hz 50 50 50 50 50
Voltage V 230 230 230/400 400 230/400/230
ELECTRICAL SPECIFICATIONS
OUTDOOR UNITS RP100B7V1/W1/T1 RP125B7W1/T1 RP200B7W1 RP250B7W1
CURRENT Nominal running
current
cooling
A - - 14.4 17.2
Maximum running
current
cooling
A - - 17.9 27.5
Starting current
cooling
A----
OUTDOOR UNITS RP100B7V1/W1/T1 RP125B7W1/T1 RP200B7W1 RP250B7W1
POWER SUPPLY V1/W1/T1 W1/T1 W1 W1
NOMINAL
DISTRIBUTION
SYSTEM VOLTAGE
Phase 1/3N/3 3N/3 3N 3N
Frequency Hz 50 50 50 50
Voltage V 230/400/230 400/230 400 400
NOTES
1 The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value, depending on the distance
and acoustic environment. For measuring conditions: please refer to item 8 of this chapter.
2 The sound power level is an absolute value indicating the ’’power’’ which a sound source generates.
3 Maximum allowable distance between indoor and outdoor unit: 25 m (for R25-35-45-60 GZ7), 70 m (for RP71-100-125B7), 50 m (for
RP200-250B7; 70 m equivalent).
Maximum allowable level difference: 15 m (for R25-35-45-60GZ7), 30 m (for RP71-100-125-200-250B7)
4 Additional refrigerant: 20g/m for total piping length > 25 m (for R25-35-45-60GZ7), 60g/m fot total piping length > 30 m (for RP200B7),
90g/m for total piping length > 30 m (for RP250B7). No additional refrigerant charge for RP71-100-125B7.
Pair Application R-407C R25-60GZ7RP71-250B7
2
Specifications
13
2
5
Split - Sky Air Outdoor Units