OUTDOOR INSTALLATION GUIDELINE
1
INSTALLING OUTDOOR UNIT
Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airow, follow the installation guidelines
below.
For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
2
DRAIN WORK
Drain work. (Heat Pump Unit Only)
1) Use drain socket for drainage.
2) If the drain port is covered by a mounting base or oor surface, place
additional foot bases of at least 30mm (1-3/16”) in height under
the outdoor unit’s feet.
3) In cold areas, do not use a drain hose with the outdoor unit.
(Otherwise, drain water may freeze, impairing heating performance.)
Wall facing one side
Wall facing one side
Walls facing two sides
Walls facing two sides
Walls facing three sides
Walls facing three sides
More than 50
More than 100
More
than 50
More
than 50
More
than 50
More
than 50
More than
50
More than
50
More than 100
More than 350
More
than 100
More
than 100
More than
150
More than
350
More than 150
More than 100
More than 300
More than 350
Side view
Side view
Top view
Top view
Top view
Top view
1200
or less
1200
or less
RXC20/25/35
RXC50/60/71
Drain water hole
Bottom frame
Drain socket
Hose (available commercially,
inner dia. 5/8"(16mm))
1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward so that
the chips do not enter the pipe.
3) Put the are nut on the pipe.
4) Flare the pipe.
5) Check that the aring is properly made.
3
FLARING THE PIPE END
(Cut exactly at
right angles.)
Flaring
Set exactly at the position shown below.
Remove burrs.
Die
A