10 | Configuration
Installer reference guide
174
EPRA14~18DAV3+W1 + ETVH16SU18+23EA6V
Daikin Altherma 3 H HT F
4P644738-1 – 2021.02
# Code Description
[3.B.1] [1-0C] Delta T heating: A minimum temperature
difference is required for the good operation of
heat emitters in heating mode.
If [2-0D] = 2, this is fixed to 10°C
Else: 3°C~10°C
[3.B.2] [1-0E] Delta T cooling: A minimum temperature
difference is required for the good operation of
heat emitters in cooling mode.
3°C~10°C
WD curve type
There are 2 methods to define the weather-dependent curves:
2-points (see "10.4.22-points curve"[4150])
Slope-Offset (see "10.4.3Slope-offset curve"[4151])
In [2.E] WD curve type, you can choose which method you want to use.
In [3.C] WD curve type, the chosen method is shown read-only (same value as in
[2.E]).
# Code Description
[2.E] / [3.C] N/A 2-points
Slope-Offset
10.5.5 Space heating/cooling
Overview
The following items are listed in the submenu:
4
Space heating/cooling
Tank
Additional zone
Main zone
User settings
[4] Space heating/cooling
[4.1] Operation mode
[4.2] Operation mode schedule
[4.3] Operation range
[4.4] Number of zones
[4.5] Pump operation mode
[4.6] Unit type
[4.7] or [4.8] Pump limitation
[4.9] Pump outside range
[4.A] Increase around 0°C
[4.B] Overshoot
[4.C] Antifrost
About space operation modes
Your unit can be a heating or a heating/cooling model:
If your unit is a heating model, it can heat up a space.
If your unit is a heating/cooling model, it can both heat up and cool down a
space. You have to tell the system which operation mode to use.