6 | Application guidelines
Installer reference guide
40
EPRA14~18DAV3+W1 + ETVH16SU18+23EA6V
Daikin Altherma 3 H HT F
4P644738-1 – 2021.02
Configuration
Setting Value
Unit temperature control:
#: [2.9]
Code: [C-07]
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
Number of water temperature zones:
#: [4.4]
Code: [7-02]
0 (Single zone): Main
External room thermostat for the main
zone:
#: [2.A]
Code: [C-05]
1 (1 contact): When the used
external room thermostat or heatpump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
Benefits
Cooling. Heatpump convectors provide, besides heating capacity, also excellent
cooling capacity.
Efficiency. Underfloor heating has the best performance with the heat pump
system.
Comfort. The combination of the two heat emitter types provides:
- The excellent heating comfort of the underfloor heating
- The excellent cooling comfort of the heatpump convectors
6.2.2 Multiple rooms – OneLWT zone
If only one leaving water temperature zone is needed because the design leaving
water temperature of all heat emitters is the same, you do NOT need a mixing
valve station (cost effective).
Example: If the heatpump system is used to heat up one floor where all the rooms
have the same heat emitters.
Underfloor heating or radiators – Thermostatic valves
If you are heating up rooms with underfloor heating or radiators, a very common
way is to control the temperature of the main room by using a thermostat (this can
either be the dedicated Human Comfort Interface (BRC1HHDA) or an external
room thermostat), while the other rooms are controlled by so-called thermostatic
valves, which open or close depending on the room temperature.
Setup
A
T
B C
a