5/13
Breadcrumb Field code Setting name Range, step
Default value
Date Value
Field settings table
Installer setting at variance with
default value
9.1.3.4 [4-06] R/W 0: Manual
1: Automatic
2: Auto red SH/ DHW ON
3: Auto red SH/ DHW OFF
4: Auto normal SH/ DHW OFF
9.1.3.5 [7-02] R/W
0: Single zone
1: Dual zone
9.1.3.6 [E-0D] R/W
0: No
1: Yes
9.1.3.7 [6-02] R/W 0~10kW, step: 0,2kW
3kW (*3)
0kW
(
*4
)
9.1.3.8 [C-02] R/W
0: No
1: Bivalent
└─ Backup heater
9.1.4.1 [5-0D] R/W (*1)
R/O (*2)
0: 230V, 1~ (*1)
1: 230V, 3~ (*1)
2: 400V
,
3~
(
*2
)
9.1.4.2 [4-0A] R/W
0: 1
1: 1/1+2 (*1) (*2)
2: 1/2
3: 1/2 + 1/1+2 in emer
g
enc
y
9.1.4.3 [6-03] R/W 0~10kW, step: 0,2kW
2kW (*1)
3kW
(
*2
)
9.1.4.4 [6-04] R/W 0~10kW, step: 0,2kW
4kW (*1)
6kW
(
*2
)
└─ Main zone
9.1.5.1 [2-0C] R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.1.5.2 [C-07] R/W
0: LWT control
1: Ext RT control
2: RT control
9.1.5.3 R/W 0: Fixed
1: WD heating, fixed cooling
2: Weather de
p
endent
9.1.5.4 R/W
0: No
1: Yes
9.1.5.5 R/W 0: 2-points
1: Slo
p
e-Offset
9.1.6 [1-00] R/W -40~5°C, step: 1°C
-15°C
9.1.6 [1-01] R/W 10~25°C, step: 1°C
15°C
9.1.6 [1-02] R/W
[9-01]~[9-00], step: 1°C
[2-0C]=0
35°C
[2-0C]=1
45°C
[2-0C]=2
65°C
9.1.6 [1-03] R/W [9-01]~min(45, [9-00])°C , step: 1°C
[2-0C]=0
25°C
[2-0C]=1
35°C
[2-0C]=2
35
°
C
9.1.7 [1-06] R/W 10~25°C, step: 1°C
20°C
9.1.7 [1-07] R/W
25~43°C, step: 1°C
35°C
9.1.7 [1-08] R/W [9-03]~[9-02]°C, step: 1°C
22°C
9.1.7 [1-09] R/W [9-03]~[9-02]°C, step: 1°C
[2-0C]=0
18°C
[2-0C]=1
7°C
[2-0C]=2
1
8
°
C
└─ Additional zone
9.1.8.1 [2-0D] R/W 0: Underfloor heating
1: Fancoil unit
2: Radiator
9.1.8.3 R/W 0: Fixed
1: WD heating, fixed cooling
2: Weather de
p
endent
9.1.8.4 R/W
0: No
1: Yes
9.1.9 [0-00] R/W [9-05]~min(45,[9-06])°C, step: 1°C
35°C
9.1.9 [0-01] R/W [9-05]~[9-06]°C, step: 1°C
65°C
9.1.9 [0-02] R/W 10~25°C, step: 1°C
15°C
9.1.9 [0-03] R/W -40~5°C, step: 1°C
-15°C
9.1.A [0-04] R/W [9-07]~[9-08]°C, step: 1°C
[2-0C]=0
18°C
[2-0C]=1
7°C
[2-0C]=2
18°C
9.1.A [0-05] R/W [9-07]~[9-08]°C, step: 1°C
22°C
9.1.A [0-06] R/W 25~43°C, step: 1°C
35°C
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
High ambient temp. for LWT add zone cooling WD curve.
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
Emitter type
Setpoint mode
Schedule
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Low ambient temp. for LWT main zone cooling WD curve.
High ambient temp. for LWT main zone cooling WD curve.
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
Emitter type
Control
Setpoint mode
Schedule
WD curve type
Low ambient temp. for LWT main zone heating WD curve.
Glycol Filled system
BSH capacity (*3)
Voltage
Configuration
Capacity step 1
Additional capacity step 2
Bivalent
Emergency
Number of zones
(*1) *6V_(*2) *9W_
(*3) ETB*_(*4) ETV*_
(*5) *X*_(*6) *H*_(*7) *SU*
(#) Only applicable in Swedish language. 4P644734-1 - 2021.02