Method of Field Set (Reset after Maintenance Inspection/Repair) Si21-205A
62 Field Setting
Address Setting
(It is Factory Set
to 1)
<Setting from the remote controller>
1. Hold down the “” button and the “” button for at least 4 seconds, to get
the FIELD SET MODE. (Indicated in the display area in the figure at below).
2. Press the “” button and select a multiple setting (A/b). Each time the button is
pressed the display switches between A and b.
3. Press the “” button and “” button to set the address.
Address can be set from 1 to 6, but set it to 1 ~ 3 and to same address as the receiver. (The
receiver does not work with address 4 ~ 6.)
4. Press the “” button to enter the setting.
5. Hold down the “” button for at least 1 second to quit the FIELD SET MODE and
return to the normal display.
Multiple Settings
A/b
When the indoor is being operating by outside control (central remote controller, etc.), it
sometimes does not respond to ON/OFF and temperature setting commands from this remote
controller. Check what setting the customer wants and make the multiple setting as shown
below.
Remote Controller Indoor Unit
Multiple Setting Remote Controller
Display
Controlled by other Air
Conditioners and
Devices
For other than on Left
A: Standard All items Displayed. Commands other than
ON/OFF and
Temperature Setting
Accepted. (1 LONG
BEEP or 3 SHORT
BEEPS Emitted)
b: Multiple display Operations set only is
displayed shortly after
execution.
All Commands Accepted (2 SHORT BEEPS)