ioLogik 2500 Series Offline Configuration Management
4-9
IO Mode Setting
Channel Mode
DIO channels can be set to one of four modes: DI, Event Counter, DO, or Pulse output. AI channels
can be set to one of five modes: ±10 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA, or 4 to 20 mA
(Burnout). AO channels can be set to one of two modes: 0 to 10 V and 4 to 20 mA.
NOTE
Since the ioLogik 2500 does not have AO channe
ls, the AO setting will only show up when the project
contains E1200 AO modules, such as the E1241.
Name
The name will be attached to the AOPC tag to help users identify channel information in MX-AOPC.
DI Setting
Filter: Software filtering is used to avoid switch bounces. The filter is configurable in multiples of 100 μs
and accepts values between 1 and 65535.
Counter Setting
Counter refers to an Event Counter channel. Counts are stored internally.
Filter
Software filtering is used to avoid switch bounces. The filter is configurable in multiples of 100 μs and
accepts values between 1 and 65535.
Initial Value
The initial value is the start value in counter mode.
Active Mode
In Active mode, the channel accepts limit or proximity switches and counts events according to the
ON/OFF status. When Rising edge is selected, the counter value increases when the attached switch is
pushed. When Falling edge is selected, the counter value increases when the switch is released. When
Both is selected, the counter value increases when the attached switch is pushed or released.