ioLogik 2500 Series Offline Configuration Management
4-22
Transparent Serial Tunnel (TCP Client)
Remote Address: The IP address of the remote host program.
Remote Port: The TCP port of the remote host program (1 to 65535; default = 1)
Transparent Serial Tunnel (TCP Server)
Listen Port: The TCP port of the ioLogik for the remote host program to establish a connection (1 to
65535; default = 4001).
Idle Timeout: The idle timeout for the ioLogik to disconnect the TCP connection (1 to 65535 min(s);
default = 10).
Modbus TCP Gateway
This function allows users to attach a serial Modbus/RTU meter to the ioLogik 2500’s serial port.
Modbus TCP Gateway
Serial Response Timeout: The timeout setting for waiting for a response from a connected serial
device (30 to 65535 ms; default = 2500).
Modbus Serial Tag
This function allows users to attach a serial Modbus/RTU meter to the ioLogik 2500’s serial port and create
the serial tags in the MX-AOPC UA Server so that a SCADA system can access this serial data directly via
OPC connections.
Serial Device
Serial
Serial
TCP
TCP
Serial
Serial
Active Tag
Serial Device
OPC DA/UA
OPC DA/UA