Moxa ioLogik 2542 [46/88] Serial port port1 port2

Moxa ioLogik 2542 [46/88] Serial port port1 port2
ioLogik 2500 Series Offline Configuration Management
4-21
NOTE
A s
horter interval time may cause a large number of data packets to be generated, resulting in higher data
fee
if you are using a pay-by-packet connection plan. The ioLogik might also experience higher system
loading and unstable performance.
Serial Port (Port1/Port2)
The ioLogik 2500 supports two serial ports for connecting to serial devices. For serial wiring instructions,
check the section Installation
Serial Communication.
Port Settings
Use port settings to set the serial ports parameters.
Mode
Supports RS-232/RS-422/RS-485
Baudrate
Supports 300, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
Stop Bits
Supports 1, 2
Flow Control
Supports None, RTC/CTS, XON/XOFF
Data Bits
Supports 5, 6, 7, 8
Parity
Supports Even, Odd, None
Operation Mode
Each port supports 4 operation modes: Transparent Serial Tunnel (TCP Client), Transparent Serial Tunnel
(TCP Server), MODBUS TCP Gateway, and Modbus Serial Tag.
Transparent Serial Tunnel (TCP Client/Server)
Transparent Serial Tunnel mode can create a TCP socket to a remote host program and transparently send
and receive data to attached legacy serial devices.
TC
Serial Device

Содержание