Fluke 1760 [100/110] Flexi current sensor 200 a 1000 a

Fluke 1760 [100/110] Flexi current sensor 200 a 1000 a
1760
Users Manual
6-22
Flexi Current Sensor 200 A/1000 A
This current probe has been designed for non intrusive, accurate ac current
measurements. Using the latest technologies (internal memory for calibration data)
provides current measurements between 2 A and 1000 A. The measurement range can be
selected in the PQ Analyze software: IAC200 or IAC1000.
Electrical Characteristics
Nominal current In: 200 A, 1000 A AC rms
Measuring ranges: 2 A – 200 A or 10 A – 1000 A ac
Peak current: 480 A, 2700 A
Max. non destructive current: Up to 2000 A rms
Intrinsic error: < ±1 % of mv
Linearity (10 % - 100 % of In): ±0.2 % of In
Conductor position influence: < ±2 % of mv, distance to measuring head
>30 mm
Error due to adjacent conductor: ±2 A (Iext = 500 A, distance to head
>200 mm)
Phase error (to reference conditions): < ± 0.5 degrees
Temperature coefficient: 0.005 % of range/ °C
Safety: 600 V CAT IV, type B sensor, pollution
degree 2
General Specifications
Cable length: 2 m
Length of measuring head: 61 cm (24 inch)
Operating temperature range: 10 °C - +70 °C
Storage temperature range: 20 °C - +90 °C
Operating humidity: 10 % - 80 % (non condensing)
Weight: Approx. 0.3 kg
Order-number: 2540489
Reference Conditions
Environment temperature range: +18 °C to +26 °C
Humidity: 20 – 75 %
Current: Nominal value In, sinusoidal waveform, 48 –
65 Hz
Distortion factor: < 1 %. No DC stray field <40 A/m, conductor
centered within the Flexi current sensor
Safety Standards
IEC/EN 61010-1 2
nd
edition
IEC/EN 61010-2-032
IEC/EN 61010-2-031

Содержание